Cooling Towers, FRP Cooling Tower, Timber Cooling Tower, RCC Cooling Tower, Belt, Screw, Roller, Slat, Chain, En Mass Conveyors

 

 
 
 

COOLING  TOWERS :-

THE ULTIMATE

Cooling Towers, FRP Cooling Tower

FRP COOLING TOWER

  YOUR SEARCH FOR AN IDEAL FRP COOLING TOWER ENDS HERE.


"THE ULTIMATE - CANARA" FRP COOLING TOWER
is uniquely designed, engineered & manufactured
for high performance reliability durability & trouble free operation
   
 

SALIENT FEATURES & SPECIFICATIONS :

CASING : The casing is manufactured of Robust FRP segments that can be easily handled during transit, installation and maintainance of tower.

FILL: The fill comprises of rigid P.V.C. UV stabilized, honeycomb, film flow type. Designed to offer highest contact area per unit volumn with least resistance to airflow.

FAN : The Axial flow fan consists of cast Aluminum or FRP variable pitch aerofoil blades fitted on a M.S. hot dip galvanized hub with S.S. 304 "U" bolts & nuts. The balanced fan assembly is mounted directly on the shaft of weather proof, flanged motor.

WATER DISTRIBUTION : Hot water is sprayed uniformly over the fill through Polypropylene / ABS nozzles fitted on a M.S. Hot dip galvanised / PVC distribution piping. The nozzles are accessible through the inspection window provided on the tower body.

DRIFT ELIMINATOR : The 2 pass drift eliminator consists if rigid PVC blades with P.P. spacers, disigned to restrict drift losses to below 0.05% of the water circulation rate. At the same time offering minimum resistance to air flow.

BASIN : The tower is fitted on FRP basin. The basin is placed on R.C.C. Pads / slabs. The basin is provided with suction, make-up, overflow & drain connections.

   
     
  TECHNICAL DATA  :

MODEL

OVERALL DIMENSIONS
MOTOR
H.P.

FAN/
MOTOR

RPM.

DRY
 WT. KGS.


OPERATING

WT. KGS.

A B C
  UT-15233 1500 460 305 0.33 2880 50 100
  UT-2205 1680 710 450 0.5 1440 80 165
  UT-2375 1680 710 450 0.75 1440 90 180
  UT-25375 1900 860 610 0.75 1440 110 275
  UT-25310 1900 860 610 1 1440 115 280
  UT-3310 2100 1015 610 1 1440 160 410
  UT-3315 2100 1015 610 1.5 1440 170 420
  UT-35315 2200 1170 760 1.5 1440 210 560
  UT-35320 2200 1170 760 2 1440 220 570
  UT-4320 2350 1320 915 2 1440 310 830
  UT-5330 2475 1625 1220 3 960 450 1250
  UT-55330 2500 1780 1375 3 960 550 1550
  UT-6330 2600 1930 1375  3 960 670 1870
  UT-6350 2600  1930 1375 5 960 700 1900
  UT-7350 2800 2235 1750 5 720 830 2730
  UT-7375 2800 2235 1750 7.5 720 850  2750
  UT-8375 2900 2540 1750 7.5 720 1000 3600
  UT-9375 3250 2850 1920  7.5 720 1200 4200
  UT-9310 3250 2850 1920 10 720 1220  4220
  UT-10310 3300 3150 1920 10 720 1400 5100
  UT-103125 3300 3150  1920 12.5  720 1425  5125
  UT-11310 3500 3460 2135 10 580 1600 6150
  UT-113125 3500 3460 2135 12.5 580 1630 6180
  UT-123125 3600 3760 2135  12.5 580 1800 7100
  UT-12315
3600 3760 2135 15 580 1830 7130

NOTE :  1) FOR HOT WATER TEMP. ABOVE 55°C. WE OFFER HONEYCOMB FILLS IN HIGH TEMP. RESISTANCE PLASTICS.
             2) IN THE INTEREST OF THE PRODUCT IMPROVEMENT WE RESERVE THE RIGHT TO IMPLEMENT CHANGES WITHOUT NOTICE.
 